Overview
Daylight Harvesting must undergo a one-time calibration procedure to establish a target light level for each fixture in the facility. The procedure establishes a dimming curve for each fixture which is automatically adjusted based on the desired light level outputs set in SiteWorx Tune. Suppose the active light level is later changed in the SiteWorx Tune software (for instance, from an Active Level of 100% to an Active Level of 80%). In that case, the target Daylight Harvesting level will automatically adjust to match the new desired output – no additional calibration is required.
If fixtures are moved, or if capital equipment is moved on the floor, the procedure should be repeated to establish new targets.
Calibration Procedure
Calibration must occur during the overnight hours when it is dark outside. The process consists of SiteWorx automatically taking over control of all lighting sensors and luminaires and overriding them to 100% output with no dimming. Each luminaire will then dim down to 1% and 0% output, then reset to 100% output.
All Tune settings will be saved and reapplied after calibration completes. However, the user cannot make any lighting changes during the calibration process.
The process takes approximately 15 seconds per sensor, so be sure to consider this when selecting a start time. Since users will not have control of the luminaires, which will be dimming down to 0% as part of the calibration, we recommend the facility be unoccupied during the calibration for safety reasons.
Additionally, the following conditions must be met to ensure proper calibration levels:
- Lighting network gateways and luminaires will remain powered during the desired calibration time.
- All luminaires, gateways, and lighting sensors are communicating with SiteWorx.
- The facility is set up in its final configuration - equipment & floor surfaces are installed and product in place (in warehousing applications).
How to Calibrate

Since users will not have control of the luminaires, which will be dimming down to 0% as part of the calibration, we recommend the facility be unoccupied during the calibration for safety reasons.
Related Articles
What is Daylight Harvesting?
Daylight Harvesting enables intelligent lighting sensors, like the SCN and DLA products, to automatically detect ambient sunlight shining through skylights and dim their light output accordingly. The dimming target is equal to the light levels in the ...
Enabling / Disabling Daylight Harvesting
Before Daylight Harvesting can be enabled, a one-time Calibration procedure must be performed remotely by SiteWorx. Enabling Daylight Harvesting for a Fixture Open the Administration Console, and click on the DH icon Click the target grey shaded ...
Troubleshooting Daylight Harvesting
Overview In SiteWorx, daylight harvesting (DH) is calibrated remotely. Moreover, the DH targets are automatically adjusted as the active and inactive levels are changed in Tune. As such, Commissioner should NOT be used to troubleshoot DH at SiteWorx ...
Getting Started - Admin Console
Only users with Admin permissions can access the Administration Console. Contact your Admin if you require access. After setting up SiteWorx Analyze, get familiar with SiteWorx Admin Console. The Administration Console contains configuration and ...
Priority of Lighting Control Features
When multiple lighting control features are active at the same time, fixtures follow a set priority to determine which setting takes effect. The order of priority from highest to lowest is: Override - This setting has the highest priority, and when ...